b'Fire HazardAS/NZS 1530.3-1999 Indices PropertiesTPC Core Ignitability Index0Range 0-20 Spread of Flame Index0Range 0-10 Heat Evolved Index0Range 0-10 Smoke Index1Range 0-10 EPS-FR Core Ignitability Index0Range 0-20 Spread of Flame Index0Range 0-10 Heat Evolved Index0Range 0-10 Smoke Index2Range 0-10 Source: AWTA Product Testing Report No. 18-006076 dated 25/5/2023 & AWTA Product Testing Report No. 23-000591 dated 20/2/2023.Material GroupGroup Numbers have been determined in accordance with testing conducted to ISO 9705 and assessment against AS 5637.1:2015. Construction requirements for Group 1 for the EPS-FR Numbers& TPC cores are shown below.EPS-FR Core Group 1:Panel thickness up to 250mm Insulating sandwich panel, nominal thickness 250mm or less. Panel core of Class SL (to AS 1366.3) expanded EPS. Clad both sides with Colorbond steel, thickness 0.4mm or greater. Panel to panel junctions require steel angles fixed to the steel skins at not more than 300mm centre, with steel rivets. Ceiling panel to panels joins require steel (stitch) rivet connecting the metal skins at not more than 1200mm centres. Smoke Growth Rate Index SMOGRA RC< 100 m 2 /s 2 . TPC Core Group 1:Panel thickness 100mm only. The interlocking joints to be filled with a fire-resistant sealant secured with 4.8 x 12mm 304 grade stainless steel rivets at 1200mm centres. The internal mitred corners in the walls and the stepped wall to ceiling junctions to be filled with a fire-resistant sealant and covered with 40 x 40 x 1.2mm pre-painted steel angle secured with 4.8 x 12mm 304 grade stainless steel rivets at 200mm centres. Panel comprising 0.6mm steel skins with a 100mm thick Phenolic composite (TPC) core. Smoke Growth Rate Index SMOGRA RC< 100 m 2 /s 2 . Source: BRANZ, Report FAR2489Issue 3 dated 23/02/2023 & BRANZ, Report FI6323-01-2 dated 25/05/2023.Certificate number: CM40365-I01-R00This certificate is only valid when reproduced in its entirety.Page 6 of 9'