b'1.TEST SPONSOR Delta Panels Pty Ltd 2828 Ipswich Road, Darra, QLD 4076, Australia 2.LIMITATION The results reported here relate only to the item/s tested. 3.TERMS AND CONDITIONS This report is issued in accordance with the Terms and Conditions as detailed and agreed in the BRANZ Services Agreement for this work. 4.DESCRIPTION OF TEST EQUIPMENT The test equipment used were LaserComp Fox 600 and FOX 801 heat flow meters.The specimen for testing is placed horizontally in the apparatus, with upwards heat flow.The hot and cold plates each have a 250 mm x 250 mm heat flux transducer embedded in their surface.The edges of the specimen are insulated from the room ambient temperature. 5.PROCEDURE The specimens were supplied by the client and consisted of two pieces of polyisocyanurate foam segment.The dimensions of the samples were approximately 600 x 600 mm.They were tested at their actual thicknesses, to the requirements of ASTM C518.6.RESULTS Table 1 Test condition set-points Nominal Upper Plate Temperature10.0C Nominal Lower Plate Temperature36.0C Nominal Difference in Temperature26.0K Nominal Mean Temperature23.0CREPORT NUMBER:ISSUE DATE:PAGE: DI10856-001-014 May 20184 of 5 branz.nz | 1222 Moonshine Rd, RD1, Porirua 5381, Private Bag 50 908, Porirua 5240, New ZealandPhone +64 4237 1170branz@branz.co.nz'