b"3.5Integrity The wall satisfied the integrity criteria for the 122 minute test duration. 3.6Deflection Measurements ThelateraldeflectionsontheunexposedfaceatthepositionsshowninFigure5were measured using a theodolite and rule. The maximum measured deflection was 65 mm away from the furnace at three quarter height and mid width of the wall (deflection point B). The results are summarised in Table 1. Table 1: Lateral Deflection Measurements of the Wall DeflectionTime (minutes) LocationDeflection (mm) 153045607590105 A-3-6-6-9-10-11-12 B-21-25-37-50-55-60-65 C'-25-29-38-55-49-50-52 C-25-30-38-55-48-49-51 D-15-20-27-47-48-50-54 E1011100 F-1-1-37-1-1-1-2 G'-15-23-39-43-37-40-47 G-16-24-41-43-37-40-48 H-20-21-29-46-51-55-60 I-20-20-23-33-39-45-54 J-19-17-19-19-20-20-22 The negative numbers are lateral deflection towards the furnace and positive numbers are lateral deflection away from the furnace. REPORT NUMBER:ISSUE DATE:PAGE:FR10430-001 ISSUE 21 June 202316 of 21 THE LEGAL VALIDITY OF THIS REPORT CAN ONLY BE CLAIMED ON PRESENTATION OF THE COMPLETE SIGNED PAPER REPORT.EXTRACTS OR ABRIDGMENTS OF THIS REPORT SHALL NOT BE PUBLISHED WITHOUT PERMISSION FROM BRANZ LTD.branz.nz | 1222 Moonshine Rd, RD1, Porirua 5381, Private Bag 50 908, Porirua 5240, New ZealandPhone +64 4237 1170branz@branz.co.nz"