b'DELTA COLDROOM RANGE0.60mm DeltaCool-EPS-FR Bracing CapacityPanel Height (m) 2.4 1.2* 4.8*Kn/m 5.0 10.0 2.5 Detail ABracing Units (BU) 100 200 50 Shear Load Transference - Shear load is transferred by rivets into the floor / ground surface or the perpendicular walls, ceiling & roof at a rate of 1.21 kN per 4.0 mm diameter rivet.* Figures for 1.2m & 4.8m high panels are extrapolated. Fixing rivets at 200mm centres complies with the 20-minuteIt is acceptable to interpolate Bracing Capacity heightsflamebarrierrequirementsanddelivers14.5kNofshearbetween 1.2m & 4.8m. For heights outside of this dimensioncapacity transfer per panel (6 on each side) horizontally, and range, Diaphragm Analysis is required to establish Bracing12.1 kN per metre in vertical joints. Limited by the ability of the Capacity. panel to transfer the shear.0.6mm DeltaCool-EPS-FR Wind Pressure (kPa)SpanPanel Thickness (mm)(mm) 50mm 75mm 100mm 125mm 150mm 175mm 200mm 250mm2000 1.84 2.92 6.11 6.11 7.35 8.01 9.21 11.552400 1.42 2.54 5.14 5.14 6.28 6.92 7.92 9.673000 0.97 1.86 3.73 3.73 4.93 5.35 6.00 7.653600 0.70 1.39 2.68 2.68 3.84 4.28 4.77 6.054200 0.51 1.06 1.96 1.96 2.87 3.33 3.79 4.814800 0.38 0.81 1.49 1.49 2.19 2.57 2.94 3.675400 0.29 0.64 1.17 1.17 1.72 2.02 2.31 2.886000 0.22 0.50 0.94 0.94 1.38 1.62 1.86 2.326600 0.17 0.39 0.77 0.77 1.14 1.34 1.54 1.917200 0.12 0.30 0.64 0.64 0.95 1.13 1.29 1.607800 0.09 0.24 0.54 0.54 0.80 0.95 1.10 1.368400 0.07 0.19 0.43 0.43 0.69 0.82 0.94 1.179000 0.06 0.15 0.35 0.35 0.60 0.71 0.82 1.019600 0.05 0.14 0.27 0.37 0.48 0.54 0.66 0.8210200 0.05 0.13 0.18 0.29 0.39 0.40 0.53 0.68The above table lists ultimate wind load pressures for strength design and the pressure corresponding to a Span/150 single span deflection for 0.6mm G300 steel skins bonded to a EPS-FR core and in accordance with Serviceability Limit State criteria as per AS 1170.0 - Table C1. The designer shall determine if Span/150 deflection ratio is appropriate for intended use. Loads for a more stringent deflection ratio can be determined by linearly proportioning the loads provided. Differential thermal effects are not incorporated in the loads provided.P: +61 7 3271 2170E: info@deltapanels.comW: www.deltapanels.com A: 731 Boundary Road, Richlands, Qld 4077ABN: 11 147 861 292Delta Panels Pty Ltd 43'