b'Fire assessment report R1.0 Appendix C Summary of supporting test data C.1Test reportRTF252619 R1.0 Table 8 Information about test report ItemInformation about test report Report sponsorDelta Panels Pty Ltd, 731 Boundary Road, Richlands QLD 4077, Australia Test laboratoryJensen Hughes Fire Testing, 409-411 Hammond Road, Dandenong, Victoria 3175, Australia. Test dateThe reaction to fire test was done on 22 October 2025. Test standardsThe test was done in accordance with AS ISO 9705:2003 (R2016).Variation to test standardsSmoke obscuration measurements were made using a helium-neon laser smoke photometer, as outlined in Annex H of ISO 9705-1:2016 in lieu of a halogen bulb and photocell apparatus as outlined under Annex E.4 of AS ISO 9705 (2016). This is not expected to prejudice the test outcome.General description of testedThe tested panels consisted of a 99 mm thick mineral wool core sandwiched between specimentwo 0.65 mm thick roll-formed painted steel skins. The panels were joined along the vertical joint, where one edge has a tongue, while the other edge has a groove. The tongue edge locks into the groove edge of the next panel. InstrumentationThe test report states that the instrumentation was in accordance with AS ISO 9705:2003 (R2016). The test specimen achieved the following resultssee Table 9. Table 9 Results summary for this test reportCriteriaResults Group number1 SMOGRA RC(in m 2 /s 2 1000)1.5Page 21 of 21 Copyright 2025 Jensen Hughes, Inc.All Rights Reserved. T1124 PAC'