b"Fire Engineering Assessment, Revision 01 DeltaCool, DeltaSecrectFix, DeltaTrim at 100 mm and 75 mm Fire Performance, Project No. 25367 25367-SFE-FEA-01-Delta Panel Fire Performance APPENDIX AASSUMPTIONS AND LIMITATIONS The following assumptions apply to the fire engineering assessments contained in this document: a.The scope of this report is limited to the assessment of the variations to the tested specimen described in Section 4.1, irrespective of specific details that may be contained on or within any referenced or non-referenced third-party project documentation. b.Thisassessmentreportappliesonlytothespecificproductsevaluated.Anymodificationstosize, construction details, applied loads, stress conditions, or edge configurations beyond those identified in this report may render its findings invalid. c.This report has been prepared based on the information provided by Delta Panels Pty Ltd. Spectra Fire Engineers have not verified the accuracy or completeness of that information and will not be responsible for any errors or omissions that may be incorporated into this report as a result.d.Except where explicitly noted herein, all standards and other documentation that are referred to within this document are assumed to be: e.For a standard or other document referenced by the NCC, the version or edition listed by the NCC revision applicable to the project, as determined by the Authority Having Jurisdiction (AHJ) and cited in this document. f.For all other codes, standards, and documentation not referenced by the NCC, the current version or edition at the time of design, or an alternative approved edition, and includes the use of any international documents having been approved by the AHJ. g.All Fire Safety Installations will be commissioned and maintained in accordance with the manufacturer's details.h.All Fire Safety Installations will be maintained to the operational capacity to which they were designed, installed, commissioned and certified. i.Except where explicitly noted herein, all Fire Safety Installations discussed within this document are assumed to be functioning correctly during a fire situation. j.Occupants will become aware of the fire through fire cues, respond to the cue, cope with the cue and attempt to avoid the fire, as intended by the NCC for safe evacuation. The following limitations apply to the fire engineering assessment contained in this document: k.Thisdocumentincorporatesallreasonableandpracticaleffortsintoproducingafireengineering assessment commensurate with the clients objectives, expectations, and operations. Guarantees cannot be provided, in producing a fire engineering documentation, that ignition or fire will not occur. Moreover, no amount of advice can guarantee that ignition or fire will not occur. l.This report addresses compliance with the National Construction Code (NCC) and related Performance Requirements. m.Requirements by others to achieve compliance with provisions not covered by the Building Act 1975 must supersede any requirements noted herein. n.The report will not include for building and contents damage, stock loss, goodwill impact, environmental impact (in a fire situation) or any loss of trade or business interruption associated directly or indirectly with a fire in these premises. o.Stipulated design criteria/parameters for engineering assessment to meet the relevant Performance Requirements of the NCC are set out herein. Where not specifically mentioned, the design, with respect to fire engineering, is expected to meet the NCC DtS provisions of all relevant codes and legislation at the time of construction and/or at the time of production of this document. p.NoliabilityisacceptedfortheapplicationoruseoftheFireEngineeringProvisionsorthedesign criteria/parameterscontainedwithinthisreportbyanypartynotengagedtoundertakedesign, construction or commissioning work associated with this development. Page 29"